XHHW-2

XHHW-2

XHHW-2 is suitable for most current industrial lighting or power wiring solutions in conduits, ducts, or other approved raceways, especially those where additional insulation toughness and moisture and heat resistance are needed.

Feature Quick View:

Direct
Burial Rated Direct Burial Rated
Corrosion Resistance Corrosion Resistance
Oil & Gas Resistant Oil & Gas Resistant
1000 V Maximum Voltage

XHHW-2 is a single-conductor building wire designed for harsh environments, including wastewater treatment plants, cogeneration power plants, and the pulp and paper industry, due to its protective insulation.

It also works well in low-voltage power and control applications, indoor and outdoor locations, raceways, aerial installations, and underground ducts.

XHHW-2 has an operational temperature range of –40°C to 90°C in wet locations and -40°C to 105°C in dry locations.

Standard Products

  • Sizes #14 AWG through 500 MCM
  • Solid or 7-strand bare copper are standard, optional stranding configurations include 19 and 37-strand
  • Up to 12 color options
  • XLP insulation is standard

KrisTech’s XHHW-2 wire meets the following standards and tests, including:

  • ASTM B-1, B-3, B-8, B-33, and B-174
  • UL 44
  • NEC NFPA 70, NEC 310, NEC 517.160
  • FED SPEC A-A-59544
  • Manufactured to comply with National Electric Code (NEC) Article 310

  • Conductors – Single conductors are available in solid or stranded configurations, and either annealed or hardened. Tin-coated copper conductors are also available.
  • Insulation – Conductors are insulated with a concentrically applied XLPE (crosslinked polyethylene) that is FT2 flame and “Oil and Gasoline Resistant I” rated. An optional VW-1 flame rating is available on request. A CT (FT4) rating in sizes #1/0 and larger is also available on request. All black insulation is rated “Sunlight Resistant.” All colored insulation is rated “Sunlight Resistant” in sizes #6 AWG and larger, and optional in sizes #8 AWG and smaller.

Print legends on the wire include the manufacturer, conductor size, voltage rating, UL symbol (if applicable), and type designation. Standard length spools are 500 or 2,500 feet.

Print Legend – KRIS-TECH WIRE CO. #XX AWG (XX MM2) XLP TYPE XHHW-2 600V AND 1000V 90C (-40C) WET OR DRY UL

Wire Paralleling and Cabling

Multiple wire runs on one reel

Colors

Choose from 12 insulation colors

Wire Striping

Add a parallel or twist stripe to any single-conductor insulated wire

Custom Print Legend

Both standard and custom print legends available

Custom Lengths

Cut and ship any length coils or reels

Packaging

Custom product labeling, shipment identification markers, and optional knock-out boxes

Labeling

Custom product identifiers available

Specifications

AWG/MCM Standard Number of Strands Optional Stranding*** Insulation Thickness (Mils) Nominal Overall Diameter – Inches (standard strands) Approx. Shipping Weight 600/2KV (Lbs./1000') Ampacity @ 90° C*
16** 1, 7 19 30 0.11 / 0.12 10 / 11 18
14 1, 7 19, 41 30 0.12 / 0.13 16 / 17 25
12 1, 7 19, 65 30 0.14 / 0.15 24 / 25 30
10 1, 7 19, 105 30 0.16 / 0.18 37 / 38 40
8 1, 7 19, 133 45 0.22 / 0.24 61 / 63 55
6 1, 7 19, 133 45 0.25 / 0.27 93 / 95 75
4 1, 7 19, 133 45 0.29 / 0.32 142 / 146 95
2 7 19, 133 45 0.38 226 130
1 19 133 55 0.44 288 145
1/0 19 133 55 0.48 357 170
2/0 19 37 55 0.53 447 195
3/0 19 37 55 0.58 556 225
4/0 19 37 55 0.64 696 260
250 37 - 65 0.71 829 290
300 37 - 65 0.76 987 320
350 37 61 65 0.81 / 0.82 1151 / 1148 350
400 37 - 65 0.90 1308 380
500 37 61 65 0.94 / 0.95 1654 / 1623 430
* Ampacity is from NEC Article 310. Check with local codes authority for guidance with your application.
** Non-UL product.
*** This stranding may require a Minimum Order Quantity, please contact KrisTech Sales for more information.


Alt test text