This single conductor building wire can be used in harsh environments, including wastewater treatment plants, cogeneration power plants, and the pulp and paper industry due to the insulation’s protective properties. It also works well in low voltage power and control applications, indoor and outdoor locations, raceways, aerial installs, and in underground ducts.
Single conductors are available in solid or stranded and annealed or hardened configurations. Tin coated copper conductors are also available.
Print legends on the wire include the manufacturer, conductor size, voltage rating, UL symbol (if applicable), and type designation. Standard length spools are 500 or 2500 feet.
KRIS-TECH WIRE CO. #XX AWG (XX MM2) XLP TYPE XHHW-2 600V AND 1000V OR RW90 600V 90C (-40C) WET OR DRY C(UL)US
AWG/MCM | Standard Number of Strands | Optional Stranding*** | Insulation Thickness (Mils) | Nominal Overall Diameter – Inches (standard strands) | Approx. Shipping Weight 600/2KV (Lbs./Mft.) | Ampacity @ 90° C* |
---|---|---|---|---|---|---|
16** | 1, 7 | 19 | 30 | 0.11 / 0.12 | 10 / 11 | 18 |
14 | 1, 7 | 19, 41 | 30 | 0.12 / 0.13 | 16 / 17 | 25 |
12 | 1, 7 | 19, 65 | 30 | 0.14 / 0.15 | 24 / 25 | 30 |
10 | 1, 7 | 19, 105 | 30 | 0.16 / 0.18 | 37 / 38 | 40 |
8 | 1, 7 | 19, 133 | 45 | 0.22 / 0.24 | 61 / 63 | 55 |
6 | 1, 7 | 19, 133 | 45 | 0.25 / 0.27 | 93 / 95 | 75 |
4 | 1, 7 | 19, 133 | 45 | 0.29 / 0.32 | 142 / 146 | 95 |
2 | 7 | 19, 133 | 45 | 0.38 | 226 | 130 |
1 | 19 | 133 | 55 | 0.44 | 288 | 145 |
1/0 | 19 | 133 | 55 | 0.48 | 357 | 170 |
2/0 | 19 | 37 | 55 | 0.53 | 447 | 195 |
3/0 | 19 | 37 | 55 | 0.58 | 556 | 225 |
4/0 | 19 | 37 | 55 | 0.64 | 696 | 260 |
250 | 37 | - | 65 | 0.71 | 829 | 290 |
300 | 37 | - | 65 | 0.76 | 987 | 320 |
350 | 37 | 61 | 65 | 0.81 / 0.82 | 1151 / 1148 | 350 |
400 | 37 | - | 65 | 0.90 | 1308 | 380 |
500 | 37 | 61 | 65 | 0.94 / 0.95 | 1654 / 1623 | 430 |