RoHS Compliant Made in USA

Scope:

Single conductor photovoltaic wire rated for interconnection wiring of grounded and ungrounded photovoltaic power systems. Approved for Direct Burial rated for a maximum continuous operating temperature between -40°C and 90°C in wet and 105°C in dry conditions.

Applicable Standards and Tests:

ASTM B-1, B-3, B33 and B-8, CSA C22.2 No. 271-11, ICEA S-95- 658/NEMA WC70, ICEA S-66-524/NEMA WC7, NEC NFPA 70, NEC 310, NEC Section 690.31, UL 44, UL 66, UL 83, UL 854, UL 1581, UL 4703 All products are spark tested at 7500 VAC unless otherwise specified.

Construction:

Conductors:

The single conductors are solid or stranded annealed or hard uncoated or tinned copper.

Insulation:

Concentrically applied XLP (crosslinked polyethylene) insulation, rated at 600V, 1000V, and 2000V. Sunlight Resistant, FV-1 flame retardant, Oil and Gasoline Resistant Cat II.

Identification and Packaging:

The wire shall be identified by surface marking indicating the manufacturer and AWG size. Products will be identified and surface printed in accordance with the UL requirements. 500 or 2500 feet length bulk reels are standard. Custom lengths, non-standard colors, AWG and custom packaging are available by request.

Value Add Service:

  • Custom lengths and put-ups
  • 12 available colors
  • Wire paralleling and cabling
  • One Pull bundled wire solution
  • Wire striping
  • Custom print legends and labels
AWGStandard Number of StrandsAlternative/Extra Flexible StrandingInsulation Thickness (inches) 600V/1 or 2KVNominal Overall Diameter - Inches (standard strands) 600V/1 or 2KVApprox. Shipping Weight (Lbs/Mft) 600V/1 or 2KVBending Radius (Inches)
147,194160/750.20"/0.23"29/350.80"/0.92"
127,196560/750.22"/0.25"39/460.88"/1.00"
107,1937 or 10560/750.24"/0.2754/610.96"/1.08"
87,1913375/850.30"/0.32"84/901.20"/1.28"
6713375/850.33"/0.35"120/1271.32"/1.4"
4713375/850.38"/0.40"174/1811.52"/1.6"
2713375/850.44"/0.46"258/2661.76"/1.84"
11913395/1050.53"/0.54"335/3452.12"/2.16"
1/01913395/1050.56"/0.58"410/4202.24"/2.32"
2/0193795/1050.61"/0.62"496/5072.44"/2.48"
3/0193795/1050.66"/0.68"610/6222.64"/2.72"
4/0193795/1050.72"/0.74752/7652.88"/2.96"
MCMStandard Number of StrandsInsulation Thickness MilsNominal Overall Diameter – InchesApprox. Shipping Weight (Lbs./Mft.)
250371200.81”1110
300371200.87”1330
350371200.92”1400
400371201.00”1590
500371201.05”1980
600611351.16”2380
750611351.27”2900