RoHS Compliant Made in USA

Scope:

Underground feeder (UF) cable is used to distribute power from buildings to outdoor fixtures like buildings, pumps, lighting, and equipment. This wire can also be used for irrigation applications and as a locating wire for underground utilities and other assets.

Applicable Standards and Tests:

  • ASTM B-1, B-3, AND B-8
  • UL 493
  • NEC ARTICLE 339

Features:

  • 600V RATED
  • DIRECT BURIAL RATED
  • 60°C MAX CONTINUING OPERATING TEMPERATURE IN WET OR DRY LOCATIONS

Construction:

Conductors:

Single conductors are solid or stranded and annealed or hardened uncoated copper.

Insulation:

Conductors are insulated with a concentrically applied PVC (polyvinyl chloride).

Identification and Packaging:

Print legends on the wire include the manufacturer, conductor size, voltage rating, UL symbol (if applicable) and type designation. Standard length spools are 500 or 2500 feet.

Print Wheel:

  • KRIS-TECH WIRE CO. E96620 (UL) TYPE UF XX/1 600V

Value Add Service:

  • CUSTOM LENGTHS AND PUT-UPS
  • 12 AVAILABLE COLORS
  • WIRE PARALLELING AND CABLING
  • WIRE STRIPING
  • CUSTOM PRINT LEGENDS AND LABELS
AWGStandard Number of StrandsInsulation Thickness (Mils)Nominal Diameter
(Inches)
Approx. Net Weight (Lbs/1000')Ampacity @ 60°C*
141, 7600.18 / 0.1926 / 2715
121, 7600.20 / 0.2135 / 3620
101, 7600.22 / 0.2449 / 5130
81, 7800.29 / 0.3180 / 8340
67800.3411855
47800.3917370
27800.4525895
119950.52330110
1/019950.56404125
2/019950.61497145
3/019950.66610165
4/019950.72758195