Scope:

Single conductor PVC (polyvinyl chloride) insulated, 600-volt dual rated TW/THW. Suitable for power, grounding and lighting in residential, commercial and industrial applications.

Applicable Standards and Tests:

ASTM B-1, B-3, and B-8, NEC 310, NFPA 70, and the California Department of Transportation (CALTRANS.) All products are spark tested at 7500 VAC unless otherwise specified.

Construction:

Conductors:

The single conductors are solid or stranded annealed, coated or bare copper.

Insulation:

Concentrically applied PVC insulation rated at -25oC to 75oC, wet or dry locations.

Identification and Packaging:

The wire shall be identified by surface marking indicating the manufacturer, AWG size, voltage rating, UL symbol, temperature rating of 75°C and type designation. 500 ft/spl.packed 4/box or 2500 feet/spl spools are standard. Custom lengths are available by request.

AWGNumber of StrandsInsulation (mils.)Alternative Insulation (mils)Nominal Overall Diameter - Inches (standard strands)Approx. Shipping Weight (Lbs/Mft)
14Solid or 730450.13/0.14 18/19
12Solid or 730450.14/0.16 28/29
10Solid or 730450 0.17/0.18 41/42
8Solid or 745600.22/0.24 72/74
6Solid or 760-0.28/0.31 105/107
47 or 13360-0.35/0.39 160/167
27 or 13360-0.41/0.45 250/265
11980-0.49324
1/01980-0.53398
2/01980-0.58496
3/01980-0.63611
4/01980-0.69755